Difference between AJ65SBTB1-16DT1 and AJ65SBTB1-16DT2
Major differences are shown below. - AJ65SBTB1-16DT1 - Rated input current approx. 5 mA - ON voltage/ON current 15 VDC or higher/3.0 mA or higher - O... More Details >>
- No:22972
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:04
-
Necessity of terminating resistors in CC-Link communication
No, it is unnecessary. Terminating resistors are only required at both ends of the network. More Details >>
- No:22966
- Release Date:2018/09/03 17:31
-
The functional grounding is applied to ensure the reliability of the communication. More Details >>
- No:23076
- Release Date:2018/09/03 17:31
-
Mixing line topologies with star topologies in the CC-Link IE Field Network
Line topologies and star topologies can be mixed. More Details >>
- No:23059
- Release Date:2018/09/03 17:31
-
Continuous executions of protocols by the QJ71C24N series CPRTCL instruction
One CPRTCL instruction can execute a maximum of eight protocols. More Details >>
- No:23050
- Release Date:2018/09/03 17:31
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
-
Applicable size for plug-in connector socket block on QJ71C24N-R4
Use the plate terminal packaged with the module. The size of the plate terminal is 1.0 mm wide with a thickness of 0.8 mm. More Details >>
- No:23043
- Release Date:2018/09/03 17:31
-
Assigning X and Y signals of AJ65SBTB1-32DT
X and Y assignments are as follows.- X0 to XF- Y10 to Y1F More Details >>
- No:23034
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Ethernet cables for the CC-Link IE Field Network
General-purpose Ethernet cables that meet the 1000BASE-T standard (category 5e or higher) can be used. We recommend double shielded cables. Recommended pro... More Details >>
- No:22989
- Release Date:2018/09/03 17:31
- Update:2019/06/27 15:47