FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > Network related products
FAQ
Keyword Search
FAQ within [ Network related products ]
-
Unit of the receive data length used by the QJ71C24N series pre-defined protocol support function
The receive data length of the variable is specified in bytes. More Details >>
- No:23037
- Release Date:2018/09/03 17:31
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
-
MODE switch setting for QJ61BT11N
The MODE switch can set the following modes.- 0 to 4: Online mode- 5 to 9: Line test mode- A to E: Hardware test modeEach mode in ascending order of set valu... More Details >>
- No:23025
- Release Date:2018/09/03 17:31
-
Transient transmission of the CC-Link IE Controller
Transient transmission is a function that allows communication with programmable controllers in other stations. Communication with programmable controllers i... More Details >>
- No:23016
- Release Date:2018/09/03 17:31
-
Connecting the CC-Link IE Field Network with a personal computer
To pursue high speeds, the CC-Link IE Field Network applies a communication control method different from that applied to the Ethernet communication for pers... More Details >>
- No:23012
- Release Date:2018/09/03 17:31
-
The number of CC-Link modules mountable with a universal model QCPU module
If the parameter is set, the following number of modules can be mounted at maximum. - Q00UJ/Q00U/Q01UCPU: Up to 2 modules - Q02UCPU: Up to 4 modules - Uni... More Details >>
- No:22981
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:20
-
Number of remote registers assigned to a remote I/O station
For "Remote Net(Ver.2 Mode)", the number of remote I/O's remote registers (RWw, RWr) is "0 Point". More Details >>
- No:22973
- Release Date:2018/09/03 17:31
-
Precautions taken when QJ61BT11 is replaced with QJ61BT11N
Set the Network Parameter as shown below. (1) If QJ61BT11 is in the remote net mode, use the remote net Ver.1 mode for QJ61BT11N. (2) If QJ61BT11 is in the... More Details >>
- No:22967
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:20
-
Extending the station-to-station distance with a CC-Link IE controller
Use the optical media converter DMS-1000SL(-DC) (manufactured by Mitsubishi Electric System & Service Co., Ltd.). You can extend the station-to-station dista... More Details >>
- No:23067
- Release Date:2018/09/03 17:31
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>
- No:23044
- Release Date:2018/09/03 17:31