A terminating resistor must be connected to the interface in order to reduce signal reflections thus preventing the signal instabilities. More Details >>
- No:22982
- Release Date:2018/09/03 17:31
-
Whether or not multiple QJ72LP25-25 modules can be mounted
No, only a single QJ72LP25-25 can be mounted (and is to be mounted on the CPU slot on a main base unit). More Details >>
- No:23042
- Release Date:2018/09/03 17:31
-
Assignment for connecting two CC-Link remote input modules (16-point type) (Remote net Ver.1 mode)
X devices will be assigned as follows. (With this setting, 32 points are occupied per station.) - Station No. 1: X100 to X11F -Station No. 2: X120 to X13... More Details >>
- No:23082
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:15
-
Difference between the CC-Link IE Controller Network and a MELSECNET/H network
The CC-Link IE Controller Network is an improved system that has a higher processing speed and a larger data capacity than the MELSECNET/H network system (PL... More Details >>
- No:22979
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:17
-
Difference between AJ65SBTB1-32DT and AJ65SBTB1-32DT2
Major differences are shown below. - AJ65SBTB1-32DT- Leakage current at OFF 0.25 mA or lower- Protection function (overload protection, overvoltage protectio... More Details >>
- No:22985
- Release Date:2018/09/03 17:31
-
SLD and FG wiring for CC-Link networks
Ground FG in each station. SLD and FG are internally short-circuited. More Details >>
- No:23020
- Release Date:2018/09/03 17:31
-
SB/SW refresh device setting with CC-Link
SB/SW uses 512 points of refresh devices. More Details >>
- No:23081
- Release Date:2018/09/03 17:31
-
Buffer memory addresses of CC-Link modules
If the remote net Ver.1 mode is used, each station number is given fixed buffer memory addresses.If the remote net Ver.2 mode is used, different buffer memor... More Details >>
- No:22992
- Release Date:2018/09/03 17:31
-
Terminating resistors for RS-485 communication of LJ71C24
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22999
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:25
-
Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>