CC-Link signals checked when an error occurs
Check the following signals.- Module error signal : X0- Host data link status signal: X1- Other station data link status signal: X3 More Details >>
- No:23021
- Release Date:2018/09/03 17:31
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
-
Limitation on the number of MELSOFT products that can be connected with the QJ71E71
In the TCP/IP connection, you can connect up to 17 MELSOFT products at the same time using a dedicated connection for system and the connections for users 1 ... More Details >>
- No:23063
- Release Date:2018/09/03 17:31
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
-
CD terminal setting of the QJ71C24N
"The CD terminal is not checked" has been set by default. More Details >>
- No:23065
- Release Date:2018/09/03 17:31
-
Identifying disconnected CC-Link stations
Identify disconnected stations using either of the following methods. (1) Select [Diagnostics] -> [CC-Link Diagnostics].from the menu in GX Works2 or G... More Details >>
- No:23053
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:59
-
Communication between a CC-Link master station and local stations
There are two modes of transient transmission, cyclic transmission and transient transmission, for the communication between a master station and a local sta... More Details >>
- No:23006
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:53
-
Precaution about MELSECNET/H connection (2)
- Set the network module mounted in system A to station number 0 (multiplexed remote master station). Set the network module mounted in system B to any sta... More Details >>
- No:23054
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:00
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
-
CC-Link slave station's flashing L.ERR LED
If the L.ERR LED flashes at irregular intervals, it may indicate that no terminating resistor has been connected or the communication is instable due to the ... More Details >>
- No:23001
- Release Date:2018/09/03 17:31