The CC-Link family products allow flexible programming and maintenance from any controllers for all the devices in connection. Such a communication, for whic... More Details >>
- No:23026
- Release Date:2018/09/03 17:31
-
Connecting the CC-Link IE Field Network with a personal computer
To pursue high speeds, the CC-Link IE Field Network applies a communication control method different from that applied to the Ethernet communication for pers... More Details >>
- No:23012
- Release Date:2018/09/03 17:31
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
-
PLC parameter setting for QJ61BT11N
If the Network Parameter is used, CC-Link communication does not need the Select setting in the I/O assignment setting of the PLC parameter.If the parameter ... More Details >>
- No:23002
- Release Date:2018/09/03 17:31
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31
-
Difference between AJ65SBTB1-32DT and AJ65SBTB1-32DT2
Major differences are shown below. - AJ65SBTB1-32DT- Leakage current at OFF 0.25 mA or lower- Protection function (overload protection, overvoltage protectio... More Details >>
- No:22985
- Release Date:2018/09/03 17:31
-
Relation between CC-Link terminals and signal lines
The following shows the relations between CC-Link terminals and signal lines. - DA : Blue -DB: White -DG: Yellow More Details >>
- No:23077
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:11
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
-
Cascade connections between hubs in the CC-Link IE Field Network
UP to 20 levels of cascade connections can be made. More Details >>
- No:23051
- Release Date:2018/09/03 17:31
- Update:2019/06/27 15:46
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>