Connecting the CC-Link IE Field Network with a personal computer
To pursue high speeds, the CC-Link IE Field Network applies a communication control method different from that applied to the Ethernet communication for pers... More Details >>
- No:23012
- Release Date:2018/09/03 17:31
-
CC-Link signals checked when an error occurs
Check the following signals.- Module error signal : X0- Host data link status signal: X1- Other station data link status signal: X3 More Details >>
- No:23021
- Release Date:2018/09/03 17:31
-
Overall cable distance and station-to-station distance in CC-Link networks
The overall cable distance and station-to-station distance depend on the version and the transmission speed. Figure 1 shows the case with Ver.1.10-compatibl... More Details >>
- No:23028
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:14
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Unit of the receive data length used by the QJ71C24N series pre-defined protocol support function
The receive data length of the variable is specified in bytes. More Details >>
- No:23037
- Release Date:2018/09/03 17:31
-
Using Ethernet UTP cables for the CC-Link IE Controller
Ethernet UTP cables cannot be used. More Details >>
- No:23062
- Release Date:2018/09/03 17:31
-
The functional grounding is applied to ensure the reliability of the communication. More Details >>
- No:23076
- Release Date:2018/09/03 17:31
-
Differences between the AJ65SBTB1-16TE and AJ65SBTB1B-16TE1
The following shows the major differences. -AJ65SBTB1-16TE - 1-wire terminal block, 1-common type - Maximum load current: 0.1 A/point -Protection fu... More Details >>
- No:23083
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:16
-
Terminating resistors for RS-422 communication of QJ71C24N
The resistance value is 330 ohm, 1/4 W. More Details >>
- No:22965
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:33
71-80 of Total 110