CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
-
Assignment for connecting two CC-Link remote input modules (16-point type) (Remote net Ver.1 mode)
X devices will be assigned as follows. (With this setting, 32 points are occupied per station.) - Station No. 1: X100 to X11F -Station No. 2: X120 to X13... More Details >>
- No:23082
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:15
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>
- No:23044
- Release Date:2018/09/03 17:31
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
-
Applicable size for plug-in connector socket block on QJ71C24N-R4
Use the plate terminal packaged with the module. The size of the plate terminal is 1.0 mm wide with a thickness of 0.8 mm. More Details >>
- No:23043
- Release Date:2018/09/03 17:31
-
What makes the ERR LED flash in a CC-Link network
A link error has occurred in one of the slave stations in connection.Master station: Check the parameter again.Slave station: Reassess the power supply, the ... More Details >>
- No:23023
- Release Date:2018/09/03 17:31
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
-
Receiving data when no receive complete code is designated (QJ71C24N)
Data are received on a received data count basis. If there is no receive complete code and variable length data is received, the data is received at every no... More Details >>
- No:23038
- Release Date:2018/09/03 17:31
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31