Compatibility between the Japanese and English versions of GX Developer
All the components other than comments in Japanese are supported. Ladder programs and parameters can be used as they are, whether or not they are created usi... More Details >>
- No:22848
- Release Date:2018/09/03 17:30
-
If the OUT instruction using the device number of the latch target device exists in a sequence program, the latched data may be overwritten by execution of t... More Details >>
- No:24783
- Release Date:2019/02/27 16:16
-
Special auxiliary relay which is always on (MELSEC-F)
M8000 More Details >>
- No:22258
- Release Date:2018/08/30 13:48
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
-
Setting a high-speed timer and a low-speed timer
In the PLC parameter setting of GX Developer, delete the start "200" of the default high-speed timer and input "0". The message indicating that "There is a d... More Details >>
- No:22943
- Release Date:2018/09/03 17:30
-
Reading a project in another format
To open a project created with GX Developer, select [Project]-> [Import file]-> [Import from xxxx format file] from the menu in GX Works2. More Details >>
- No:22952
- Release Date:2018/09/03 17:30
- Update:2018/09/25 11:56
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
-
Using GX Logviewer's realtime monitor function on multiple personal computers
Up to two realtime monitor windows can be used for monitoring.If each of two personal computers monitors one monitor window, two personal computers can be co... More Details >>
- No:22881
- Release Date:2018/09/03 17:30
-
Time out error in the communication test of MX Component
The possible causes are as follows. - Incorrect setting with a personal computer or an Ethernet interface module Check the IP address, network number, sta... More Details >>
- No:22934
- Release Date:2018/09/03 17:30
- Update:2018/09/25 09:49
-
Maximum number of characters in a comment that can be transferred to a FX3U series
As project data, up to 32 one-byte characters (16 two-byte characters) can be input to each global device comment. However, the maximum number of characters ... More Details >>
- No:24700
- Release Date:2019/02/27 08:59