Connectable number of MODBUS RTU (ME96SS series).
It is connectable with up to 31 units. It is necessary to prepare at least 3 PCs for connecting with 64 units. (31 units + 31 units + 2 units) More Details >>
- No:22190
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Recommended update period (ME96SS series).
The expected lifetime is 10 years. Is recommended to replace the device every 10 year. However the environment of installed location, such as temperature ... More Details >>
- No:22154
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:02
- Category: Electrical Indicators
-
Response speed of the analog output (ME96SS series).
The response speed of the analog output is 2 seconds or less. The response speed of harmonic measurement is 10 seconds or less. More Details >>
- No:22157
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:12
- Category: Electrical Indicators
-
Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
- Category: Electrical Indicators
-
Check the measurement values using MODBUS RTU communication
It is possible to check them using the Data Acquisition Software EMU4-SW1. It is available for download without payment from the following Web site. ... More Details >>
- No:37812
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Checking the set values (ME96SS series).
Pressing the buttons of the “Set” for 2 seconds or more shifts the mode to the “Setting Value Confirmation Mode”. It is impossible to change the set values... More Details >>
- No:22165
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
- Category: Electrical Indicators
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators
-
LCD COM is flashing (ME96SS series).
A reason varies with the connection situation of options. (Please refer to the section 6 of the User’s Manual.) In case of MODBUS RTU Error content: ... More Details >>
- No:22186
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:20
- Category: Electrical Indicators
-
Installation compatibility with ME96NSR (ME96SS series).
They are the same dimensions. (Dimensions of an installation hole is 92 mm in length and width. Install this model two points with mounting brackets.) More Details >>
- No:22160
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators