Power Management Meters
FAQ within [ Power Management Meters ]
-
Regardless of setting, the value of the default digit length is replied. When the register address “1304” for 6-digit display is set, the value varies w... More Details >>
- No:22189
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:26
- Category: Electrical Indicators
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
- Category: Electrical Indicators
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
Availability for direct measurement of 400V loads (ME96SS series).
This model is available for direct measurement of 400V loads at the STAR connection in Three-phase 3-wire system. More Details >>
- No:22150
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators
-
Sample program for MODBUS RTU communication (ME96SS series)
Sample programs are described in Programming Manual. Please refer to MODBUS Interface specifications(LSPM-0075) The programming manual can be downloaded fr... More Details >>
- No:24805
- Release Date:2019/03/27 12:12
- Category: Electrical Indicators
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56
- Category: Electrical Indicators
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Standards for this model (ME96SS series).
This model is compliant with CE marking, UL standard, KC Mark and FCC/IC. More Details >>
- No:22146
- Release Date:2018/08/27 16:41
- Update:2020/04/10 14:27
- Category: Electrical Indicators
41-50 of Total 57