- FAQ > Low-voltage Power Distribution Products > Power Management Meters > Electrical Indicators
FAQ
Keyword Search
FAQ within [ Electrical Indicators ]
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
-
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
- No:37704
- Release Date:2020/01/29 18:36
-
Validation method for communication function (ME96SS series).
This model has the test function of the communication operation. For detail, refer to User's Manual: Detailed Edition for setting. More Details >>
- No:22180
- Release Date:2018/08/27 16:41
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
-
Compatibility between present model and new model for the CC-Link (ME96SS series).
The CC-Link is compatible with the new model. More Details >>
- No:22151
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:51
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41