Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
-
Regardless of setting, the value of the default digit length is replied. When the register address “1304” for 6-digit display is set, the value varies w... More Details >>
- No:22189
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:26
-
Measuring received energy and the transferred energy (ME96SS series).
It is possible to measure the received energy and the transferred energy separately. More Details >>
- No:22176
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:53
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
-
When the AC waveform distorted due to harmonics, the value changes. (For AC without harmonics, the calculated value will match with the displayed value.) A... More Details >>
- No:22178
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:56
-
Checking non-displayed digit of active energy (ME96SS series).
Pressing buttons of the “+” and the “-” at the same time on the measurement screen for 2 seconds shifts the unit of active energy as follows. The measured ... More Details >>
- No:22172
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:44
-
Sample program for MODBUS RTU communication (ME96SS series)
Sample programs are described in Programming Manual. Please refer to MODBUS Interface specifications(LSPM-0075) The programming manual can be downloaded fr... More Details >>
- No:24805
- Release Date:2019/03/27 12:12
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56