FAQ
FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>
-
How to read the device memory in GX Works2
Select [Online] -> [Read from PLC] from the menu and check "Device Memory" in the file list in the window and then execute PLC read. More Details >>
- No:22621
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
I cannot select [Transfer Setup] in GX Developer because it is displayed in gray.
You cannot select the item while the programmable controller is being monitored. Execute [Close all windows] of [Window] from the tool bar, and check if Tra... More Details >>
- No:22955
- Release Date:2018/09/03 17:31
- Update:2018/09/25 12:11
- Category: Engineering Software
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
How to copy comments from GX Developer to GX Works2
Launch GX Works2, select [Project] -> [Open Other Project], and read the data created with GX Developer. Copy the comment from the list of device comme... More Details >>
- No:22526
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:32
- Category: MELSEC-Q Series
-
Error in simulation in GX Works2
This problem can be workarounded by upgrading software products made by other companies to the latest version or uninstalling them.For more details, refer to... More Details >>
- No:22570
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
The error code "2100" is "SP.UNIT LAY ERR.". This error may be caused by one of the following factors. (1) An intelligent function module is assigned as a... More Details >>
- No:22725
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:02
- Category: MELSEC-L Series
-
Checking the amount of free space of the memory in GX Developer/GX Works2
Select [Tool] -> [Confirm Memory Size] to check the amount. More Details >>
- No:22851
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
- Category: MELSEC-F Series , Main Unit , Accessories