Availability of step ladders for FX in L series
Step ladders are not available in LCPU. There is no alternative function. More Details >>
- No:22752
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Behavior of sequence program in event of momentary power failure in LCPU
(1) When it happened no longer than the allowable momentary power failure time. The module records an error log and suspends the operation processing. Ho... More Details >>
- No:22756
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:43
- Category: MELSEC-L Series
-
Number of points used for I/O assignment of LCPU built-in I/O function
X00 to X0F and Y00 to Y07 are sorted for each function. For more details, refer to "MELSEC-L CPU Module User's Manual (Built-In I/O Function)". More Details >>
- No:22762
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Simultaneous broadcast reception setting for built-in Ethernet port LCPU
To receive simultaneous broadcast using UDP, set the parameters as follows. - Destination IP Address: FF.FF.FF.FFh - Destination Port No.: Other than FFFFh (... More Details >>
- No:22772
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Maximum number of connectable modules to LCPU when it is not extended
Up to 10 modules can be connected in the system as a whole except for the power supply module, CPU module, display unit, RS232C adapter, and END cover. Some ... More Details >>
- No:22775
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Restriction on the use of CPU when branch module and extension module are used
Use L series CPU modules whose first 5 digits of the serial number are "13072" or later. More Details >>
- No:22800
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Sampling cycle of L60TCTT4(BW) and L60TCRT4(BW)
It is selectable from the following. - 500 ms/4 channels (Default)- 250 ms/4 channels More Details >>
- No:22824
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
MX Sheet Version 2's compatibility with 64-bit Windows 7
Yes. More Details >>
- No:22866
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
CW Workbench can be purchased from Mitsubishi Electric. We also accept license applications. More Details >>
- No:22880
- Release Date:2018/09/03 17:30
- Category: Engineering Software
101-110 of Total 1123