FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Settings required for transient transmission
The routing parameter settings are required for transient transmission to the CPU module with another network No. The request source station, relay station,... More Details >>
- No:22995
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:40
- Category: Network related products
-
Yes. More Details >>
- No:22998
- Release Date:2018/09/03 17:31
- Category: Network related products
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
- Category: Network related products
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
- Category: Network related products
-
The CC-Link family products allow flexible programming and maintenance from any controllers for all the devices in connection. Such a communication, for whic... More Details >>
- No:23026
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
- Category: Network related products
-
Receiving data when no receive complete code is designated (QJ71C24N)
Data are received on a received data count basis. If there is no receive complete code and variable length data is received, the data is received at every no... More Details >>
- No:23038
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Connecting terminating resistors for CC-Link communication
Connect terminating resistors to both ends of physical cables.A master station is not necessarily required to be connected to either end of its network. More Details >>
- No:23046
- Release Date:2018/09/03 17:31
- Category: Network related products
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
- Category: Network related products
181-190 of Total 1123