FAQ


FAQAbout Products

FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Regarding protocol creation of Predefined Protocol Support Function
You can not create a protocol for the other device. More Details >>
- No:39293
- Release Date:2023/02/13 15:38
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding "_ U" in Application Instruction
It means an instruction that handles BIN 16 bit and BIN 32 bit unsigned data. Example:ADD _ U More Details >>
- No:39295
- Release Date:2023/02/13 16:37
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding device comment output to Data Logging Files
Device comments can not be output to data logging files. More Details >>
- No:39321
- Release Date:2023/02/14 09:00
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the number of FX5-4A-ADP connections
Up to 4 FX5-4A-ADPs can be connected to an FX5U/FX5UC/FX5S CPU module. To connect 3 or more FX5-4A-ADPs, the FX5-4A-ADP must have a serial number S/N: 224... More Details >>
- No:39348
- Release Date:2023/02/15 10:16
- Category: MELSEC iQ-F Series , CPU Module , Analog
-
How to use variable analog potentiometers in FX3S
Numerical value data 0 to 255 corresponding tothe scale position is stored in the special data register. You can create the analog timer (volume type) by sp... More Details >>
- No:22279
- Release Date:2018/08/30 13:48
- Update:2019/02/14 10:05
- Category: MELSEC-F Series , Main Unit , Analog Control
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Duplicated coil errors that can be checked with GX Works3
When an SET instruction and RST instruction use a single device, no duplicated coil error is detected. More Details >>
- No:22456
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:33
- Category: MELSEC iQ-R Series
-
Cause of file register reset by latch clear operation in universal model QCPU
If Latch (1) is set in the device setting of PLC parameter, the contents of file registers are cleared by latch clear operation. Set Latch (2) to maintain t... More Details >>
- No:22584
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:31
- Category: MELSEC-Q Series
-
Communication between built-in Ethernet port QCPU modules
The following communication methods are available between built-in Ethernet port QCPU modules. - Socket communications are possible. - Communications equ... More Details >>
- No:22586
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:33
- Category: MELSEC-Q Series
-
TCP retransmission timer setting for built-in Ethernet port LCPU
For the built-in Ethernet port in the L series CPU, the TCP retransmission timer setting is fixed and unchangeable. The retransmission occurs six times. The... More Details >>
- No:22745
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:52
- Category: MELSEC-L Series