Operation error at the execution of a BIN instruction
Keep SM722 ON or correct the program so that any one of the ten numbers 0 to 9 is stored in each digit of the source data.An operation error occurs when data... More Details >>
- No:22635
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Q series device data held in the case of a power failure
The data in the devices assigned to Latch (1) or Latch (2) in the "Device Setting" window ([PLC Parameter] -> [Device Setting] window) is held when a pow... More Details >>
- No:22638
- Release Date:2018/09/03 17:29
- Update:2018/09/21 11:37
- Category: MELSEC-Q Series
-
Accessing file registers from the built-in Ethernet port QCPU using A-compatible 1E frames
The QnUDE(H)CPU modules with serial numbers with upper 5 digits of "14112" or later indicate compatibility with the function. The accessible device range is ... More Details >>
- No:22645
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Software required for MX Sheet
MX Component and EXCEL are required. More Details >>
- No:22646
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
It means that in an ambient temperature of 25 degrees Celsius, an error per day falls within the range of "delay of 2.57s" to "advance of 5.27s". "TYP.+2.22... More Details >>
- No:22651
- Release Date:2018/09/03 17:29
- Update:2018/09/26 16:53
- Category: MELSEC-Q Series
-
QCPU built-in Ethernet port setting when using the simple PLC communication function
The following settings are required for the "Open Setting" for the number of connected external devices. - Protocol: "UDP" - Open System: "MELSOFT connecti... More Details >>
- No:22654
- Release Date:2018/09/03 17:29
- Update:2018/09/21 12:02
- Category: MELSEC-Q Series
-
Recommended cables for the MODBUS(R) interface module QJ71MT91
For 100BASE-TX, shielded twisted pair cables (STP cables) with category 5 can be used.For 10BASE-T, Straight and unshielded twisted pair cables (UTP cables) ... More Details >>
- No:22659
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Ethernet communication after the replacement of an external device
Personal computers have different MAC addresses and an Ethernet module hold a MAC address. Hence the MAC address that the Ethernet module currently holds is ... More Details >>
- No:22665
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Accessible numbers of devices in one message are shown below.- 2000 coils and inputs for reading- 125 input registers and holding registers for reading- 1968... More Details >>
- No:22668
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
The numbers of POUs and steps of "Allocate Memory for 'Online Change'" in GX Works2
The maximum number of steps that an online change can process at a time is 512. More Details >>