Copying statements and notes of GX Developer
Notes and statements are batch managed in the program file. It is impossible to copy notes and statements alone. More Details >>
- No:22853
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Print function of GX Developer
The Print Preview window of GX Developer is a function for checking a print image, made to a specification that allows display of only the first page. A page... More Details >>
- No:22870
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Difference between QJ61BT11 and QJ61BT11N
QJ61BT11N supports Version 2 (expanded cyclic setting), the setting for refreshing/forced clearing a slave station data when the switch on a programmable con... More Details >>
- No:22964
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:16
- Category: Network related products
-
Terminating resistors for RS-422 communication of QJ71C24N
The resistance value is 330 ohm, 1/4 W. More Details >>
- No:22965
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:33
- Category: Network related products
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Difference between the CC-Link IE Controller Network and a MELSECNET/H network
The CC-Link IE Controller Network is an improved system that has a higher processing speed and a larger data capacity than the MELSECNET/H network system (PL... More Details >>
- No:22979
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:17
- Category: Network related products
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Connecting terminating resistors for CC-Link communication
Connect terminating resistors to both ends of physical cables.A master station is not necessarily required to be connected to either end of its network. More Details >>
- No:23046
- Release Date:2018/09/03 17:31
- Category: Network related products
-
How to check the error history of the QJ71C24N with GX Developer
You can check the error history in the module detailed information in the system monitor of GX Developer. More Details >>
- No:23064
- Release Date:2018/09/03 17:31
- Category: Network related products