FAQ within [ Controllers ]
-
Periodic replacement is recommended. For example, standard life of FX3U-32BL is 5 years (at ambient temperature of 25). The life of the battery changes wit... More Details >>
- No:22262
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , Accessories
-
Programming software and tool for the FX2N-10GM/FX2N-20GM
Use the "FX-PCS-VPS/WIN" software for personal computer or the "E-20TP-SET0" handy programming panel. More Details >>
- No:25014
- Release Date:2019/04/23 11:16
- Category: MELSEC-F Series , Engineering Software , Accessories
-
In order for the programmable controller to receive input pulses completely, the ON duration and OFF duration of inputs in the programmable controller requir... More Details >>
- No:24704
- Release Date:2019/02/27 09:00
- Category: MELSEC-F Series , Main Unit , High-Speed Counting
-
Regarding the maximum number of controllable axes of the bulit-in positioning function
Up to 4 axes can be controlled. Please use a transistor output type CPU module. (By adding a high speed pulse input/output module, maximum 12 axes (CPU bui... More Details >>
- No:22300
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:52
- Category: MELSEC iQ-F Series , CPU Module , Motion/Positioning
-
Regarding checking latch settings
You can find it in the Advanced Settings section of GX Works3. Use the following procedure to display the Device (High Speed) settings. From the GX Wor... More Details >>
- No:44364
- Release Date:2024/03/27 16:05
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
One FX3U-ENET-ADP can be connected at the last stage (left end) of adapters for the FX3GC series. * The FX3U-ENET-ADP is a communication special adapter and... More Details >>
- No:24967
- Release Date:2019/04/23 07:18
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
Ver2.00 or later is applicable. (GX Works2 with Ver. 1.87R or later is applicable.) The version of main units can be checked with the last three digits of t... More Details >>
- No:24922
- Release Date:2019/04/17 11:41
- Category: MELSEC-F Series , Main Unit
-
Regarding the frequency of high-speed counters
The maximum frequency of the FX5U/FX5UC CPU module is 200kHz and the maximum frequency of the FX5S/FX5UJ CPU module is 100 kHz. More Details >>
- No:22312
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:18
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding comparison of Strings
Use the string comparison instructions LD$□, AND$□, OR$□. □contains =, <>, >, < =, <, > =. More Details >>
- No:39355
- Release Date:2023/02/15 13:03
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding Data Logging File Storage Format
It's possible. For the firmware and software versions of the corresponding CPU units, refer to the respective manuals. More Details >>
- No:39308
- Release Date:2023/02/13 16:44
- Update:2023/02/14 09:01
- Category: MELSEC iQ-F Series , CPU Module