Regarding Input Response Frequency Difference between FX5-2HC/ES and Conventional Model (FX3U-2HC)
The input response frequencies of the FX5-2HC/ES and FX3U-2HC differ as shown below. FX5-2HC/ES・・・2MHz FX3U-2HC・・・200kHz More Details >>
- No:44340
- Release Date:2024/03/20 13:31
- Category: MELSEC iQ-F Series , High-Speed Counter
-
Regarding FX5-2HC/ES restrictions
The FX5-2HC/ES must be connected to the eighth module from the power supply module (CPU Module, expansion power supply module, built-in power supply I/O Modu... More Details >>
- No:44339
- Release Date:2024/03/20 13:25
- Category: MELSEC iQ-F Series , High-Speed Counter
-
Regarding the differences between the FX5-2HC/ES and the conventional FX3U-2HC input formats
The FX5-2HC/ES supports differential line drivers (5 V) only. The FX3U-2HC supports open collectors (24 V/12 V/5 V) and differential line drivers (5 V). ... More Details >>
- No:44338
- Release Date:2024/03/26 09:02
- Category: MELSEC iQ-F Series , High-Speed Counter
-
Regarding use of the FTP Server Auto Transfer Function with Other Functions
Be careful when using the FTP server auto transfer function in combination with the following functions. ・FTP client (FTPPUT instruction) The function exe... More Details >>
- No:44336
- Release Date:2024/03/20 13:28
- Category: MELSEC iQ-F Series , CPU Module
-
The following points are different for the iQ-F series. ・Error History If the FX5 CPU Module is turned off, the error history is cleared. ・Setting detail... More Details >>
- No:44335
- Release Date:2024/03/20 13:21
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding automatic transfer of Data Logging Files
Data logging file transfer (FTP server auto transfer) is supported with the following firmware versions. ・FX5U/FX5UC CPU Module Ver. 1.300 or later ・FX5U... More Details >>
- No:44334
- Release Date:2024/03/20 13:30
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding restrictions on the external input/output forced ON/OFF function
The following restrictions apply to the external input/output forced ON/OFF function. ・Since RUN contact setting is RUN/STOP by external signal, forced ON/O... More Details >>
- No:44332
- Release Date:2024/03/20 12:58
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding specifications of the forced ON/OFF function for external input/output
The following points are different for the iQ-F series. ・All output disabled flag (SM8034) When SM8034 is ON, the all output disabled flag is given priorit... More Details >>
- No:44331
- Release Date:2024/03/20 12:54
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding forced ON/OFF function for external input/output
The "Forced ON/OFF function for external input/output" that forces X/Y devices to turn on/off from GX Works3 is supported with the following firmware version... More Details >>
- No:44330
- Release Date:2024/03/20 12:56
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding setting the FX5 CPU Module that does not support the simple CPU communication function
When connecting 2 FX5 CPU Modules (firmware version 1.110 or later) that support the Simple CPU communication function and 2 FX5 CPU Modules (firmware vers... More Details >>
- No:44329
- Release Date:2024/03/20 13:35
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication