FAQ within [ Controllers ]
-
Communication between CPU modules established by QJ71E71
The communication between QJ71E71 series modules can be established if READ/WRITE instructions are used. More Details >>
- No:23036
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Assigning X and Y signals of AJ65SBTB1-32DT
X and Y assignments are as follows.- X0 to XF- Y10 to Y1F More Details >>
- No:23034
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
- Category: Network related products
-
CC-Link IE Controller cable standard
Use the cables that meet the IEC60793-2-10 Types A1a.1 optical fiber standard. The connectors are LC (duplex) connectors. Two cores are required.The core di... More Details >>
- No:23032
- Release Date:2018/09/03 17:31
- Update:2018/09/27 12:14
- Category: Network related products
-
Overall cable distance and station-to-station distance in CC-Link networks
The overall cable distance and station-to-station distance depend on the version and the transmission speed. Figure 1 shows the case with Ver.1.10-compatibl... More Details >>
- No:23028
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:14
- Category: Network related products
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
- Category: Network related products
-
The CC-Link family products allow flexible programming and maintenance from any controllers for all the devices in connection. Such a communication, for whic... More Details >>
- No:23026
- Release Date:2018/09/03 17:31
- Category: Network related products
-
SLD and FG wiring for CC-Link networks
Ground FG in each station. SLD and FG are internally short-circuited. More Details >>
- No:23020
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Effect on sequence scans in MELSECNET/H networks
It is necessary to reduce the link refresh time of the MELSECNET/H network in order to reduce the scan time. The link refresh time can be reduced by reducin... More Details >>
- No:23018
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:27
- Category: Network related products
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
- Category: Network related products
861-870 of Total 1082