FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Compliance with SEMI-F47 for L series power supply module
Use the following power supply module with an input power of 200 VAC for compliance with SEMI-F47. - Power supply module: L61PWith an input power of 100 VAC,... More Details >>
- No:22768
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Remedy to an error message when performing online change in LCPU
After data is written to the program cache memory (SRAM), it is automatically transferred to the program memory (flash ROM). Therefore, additional online cha... More Details >>
- No:22763
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:50
- Category: MELSEC-L Series
-
KeepAlive setting for built-in Ethernet port in LCPU
The KeepAlive setting for the built-in Ethernet port in the L series is fixed. The setting is unchangeable. More Details >>
- No:22760
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The number of LCPU extension blocks
(1) The number of modules to be connected- Main block: up to 10 modules- Extension block: up to 11 modules(2) The number of extension blocks- L02CPU, L02CPU-... More Details >>
- No:22750
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Communication data code of the MC protocol for the built-in Ethernet port in LCPU
The communication data code is selectable by the communication data code setting in [Parameter] -> [PLC Parameter] -> [Built-in Ethernet Port Setting]. More Details >>
- No:22735
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:22
- Category: MELSEC-L Series
-
The contents of the standard RAM and latch devices are not erased if the battery replacement is completed within three minutes, which is the backup power tim... More Details >>
- No:22733
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Use of an A-compatible 1E frame for the built-in Ethernet port of LCPU
The built-in Ethernet port in the L series is compatible only with a QnA-compatible 3E frame of the MC protocol. An A-compatible 1E frame is not supported. More Details >>
- No:22731
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Detecting the connection between a built-in Ethernet port QCPU and hub
You can check the connection to the hub with bit 10 of the special register SD1288. When bit 10 of the SD1288 is on, the QCPU is in connection with the hub. More Details >>
- No:22712
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
How to check the capacity of the file registers in use
The capacity file registers currently have can be checked in the file register setting section ([PLC Parameter] -> [PLC File] tab). More Details >>
- No:22694
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:19
- Category: MELSEC-Q Series
-
Cables connected to the Ethernet port on the universal model QCPU
If a direct connection is made, either type can be used.If making a connection via a hub, use a straight cable. More Details >>
- No:22690
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
881-890 of Total 1123