Controllers
FAQ within [ Controllers ]
-
Versions of built-in Ethernet port LCPU compatible with SNTP function
The initial version and subsequent versions of L series CPU support the SNTP function. More Details >>
- No:22769
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Compliance with SEMI-F47 for L series power supply module
Use the following power supply module with an input power of 200 VAC for compliance with SEMI-F47. - Power supply module: L61PWith an input power of 100 VAC,... More Details >>
- No:22768
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Behavior of sequence program in event of momentary power failure in LCPU
(1) When it happened no longer than the allowable momentary power failure time. The module records an error log and suspends the operation processing. Ho... More Details >>
- No:22756
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:43
- Category: MELSEC-L Series
-
Method to prevent the BAT.LED from turning on
To prevent an LED from turning on when an error occurs, set 0 to the relevant factor number setting area (4 bits for each) in SD207 to SD209. To disable the ... More Details >>
- No:22754
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
L63P compatibility with L series CPU packages
It is possible to remove L61P and use L63P. More Details >>
- No:22742
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Use SP.FWRITE instruction to save the data to an SD memory card in CSV format. More Details >>
- No:22727
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Compatibility between the A series modules and Q series modules
When an ACPU module is replaced with a QCPU module, programs for the ACPU module can be used by changing the PLC type in GX Developer. However, the programs ... More Details >>
- No:22696
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:21
- Category: MELSEC-Q Series
-
How to launch GX Works2 or other tools after installing iQ Works
The tools can be launched individually. More Details >>
- No:22693
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Input derating is the percentage of simultaneous ON points, one of the specifications applied when input modules are used. When QX42 is used in a temperatur... More Details >>
- No:22692
- Release Date:2018/09/03 17:29
- Update:2018/10/03 16:23
- Category: MELSEC-Q Series
-
Remedy for the division-related operation error
The operation error occurs when the divisor is 0.Create a program in which a comparison operation instruction or another method executes a division instructi... More Details >>