FAQ
FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Connecting AJ65BT-R2N to a GOT
Yes.When connecting a GOT, set the mode setting switch of AJ65BT-R2N to "5" (MELSOFT connection mode). More Details >>
- No:23047
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Receiving data when no receive complete code is designated (QJ71C24N)
Data are received on a received data count basis. If there is no receive complete code and variable length data is received, the data is received at every no... More Details >>
- No:23038
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
- Category: Network related products
-
CC-Link IE Controller cable standard
Use the cables that meet the IEC60793-2-10 Types A1a.1 optical fiber standard. The connectors are LC (duplex) connectors. Two cores are required.The core di... More Details >>
- No:23032
- Release Date:2018/09/03 17:31
- Update:2018/09/27 12:14
- Category: Network related products
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
- Category: Network related products
-
SLD and FG wiring for CC-Link networks
Ground FG in each station. SLD and FG are internally short-circuited. More Details >>
- No:23020
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Effect on sequence scans in MELSECNET/H networks
It is necessary to reduce the link refresh time of the MELSECNET/H network in order to reduce the scan time. The link refresh time can be reduced by reducin... More Details >>
- No:23018
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:27
- Category: Network related products
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Terminating resistors for RS-485 communication of LJ71C24
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22999
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:25
- Category: Network related products