Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
- Category: MELSEC-L Series
-
Simultaneous broadcast transmission setting for built-in Ethernet port LCPU
To send simultaneous broadcast using UDP, set the parameters as follows.- Destination IP Address: FF.FF.FF.FFh - Destination Port Number: Other than FFFFh (S... More Details >>
- No:22785
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
SNTP communication error in built-in Ethernet port LCPU
The error does not affect the CPU time. The CPU time is not set when a communication error occurs. More Details >>
- No:22783
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Q6BAT. More Details >>
- No:22780
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Precautions for use of SD memory card
Yes. Note that SD memory cards are formatted at the factory. If an SD memory card needs to be reformatted, format it using the CPU module. More Details >>
- No:22779
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Application of RS-232 adapter L6ADP-R2
This adapter is used to add a serial port to the L series CPU. It is not a serial communication module. It is used for serial communication between a device ... More Details >>
- No:22778
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Number of points used for I/O assignment of L26CPU-(P)BT built-in CC-Link function
It is fixed to 32 points from 10 to 2F. More Details >>
- No:22777
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The conversion speed is as follows. - High speed: 20 microseconds per channel- Medium speed: 80 microseconds per channel- Low speed: 1 millisecond per channel More Details >>
- No:22776
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Maximum number of connectable modules to LCPU when it is not extended
Up to 10 modules can be connected in the system as a whole except for the power supply module, CPU module, display unit, RS232C adapter, and END cover. Some ... More Details >>
- No:22775
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Execution of the SOCRMODE instruction in the same connection during socket communication of LCPU
It can be executed for the same connection number. When data exist in the socket communication receive data area and the SOCRMODE instruction is executed, va... More Details >>
- No:22771
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series