FAQ


FAQAbout Products

FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
- Category: MELSEC-L Series
-
Simultaneous broadcast transmission setting for built-in Ethernet port LCPU
To send simultaneous broadcast using UDP, set the parameters as follows.- Destination IP Address: FF.FF.FF.FFh - Destination Port Number: Other than FFFFh (S... More Details >>
- No:22785
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
SD1284 of LCPU with built-in Ethernet port
The bits 0 to F of the special register SD1284 (Open request signal) correspond to the connection numbers 1 to 16. When the open request is sent, the corresp... More Details >>
- No:22784
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Method to prevent the BAT.LED from turning on
To prevent an LED from turning on when an error occurs, set 0 to the relevant factor number setting area (4 bits for each) in SD207 to SD209. To disable the ... More Details >>
- No:22754
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Availability of step ladders for FX in L series
Step ladders are not available in LCPU. There is no alternative function. More Details >>
- No:22752
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
How to launch GX Works2 or other tools after installing iQ Works
The tools can be launched individually. More Details >>
- No:22693
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Parameter settings required to use the MODBUS(R) interface module as a slave station
If preset initial values are used, parameters do not need setting.If changing the basic parameter or MODBUS(R) device assignment parameter, use a sequence pr... More Details >>
- No:22680
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Runtime license for MX Component
A runtime license is required for all personal computers on which MX Component operates. More Details >>
- No:22657
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
The following Diatrend cable can be used.- DQ-U2 More Details >>
- No:22623
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
How to display the list of device comments in GX Works2
Double-click "Global Device Comment" in the Project view to display the list. More Details >>
- No:22606
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
951-960 of Total 1110