Regarding Data Register Byte Splitting
Use the WTOB instruction. More Details >>
- No:40022
- Release Date:2023/08/24 14:32
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding CC-Link IE Filed Basic Protocol Mixing
It is possible to mix CC-Link IE Filed Basic and general-purpose Ethernet communication. More Details >>
- No:40031
- Release Date:2023/08/24 14:40
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding Display Module Support
In the iQ-F series, there is no lineup of display modules. Consider usingweb server function. More Details >>
- No:40045
- Release Date:2023/08/24 15:53
- Update:2023/08/24 15:56
- Category: MELSEC iQ-F Series , CPU Module
-
The following points are different for the iQ-F series. ・Error History If the FX5 CPU Module is turned off, the error history is cleared. ・Setting detail... More Details >>
- No:44335
- Release Date:2024/03/20 13:21
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the MQTT communication function retransmission function
No, there is no function to resend all the data that could not be sent. By setting Retain and QoS from FB, it is possible to resend only the latest message. More Details >>
- No:44368
- Release Date:2024/03/27 16:56
- Category: MELSEC iQ-F Series , Network/Communication
-
Yes, it is possible. Please consider functions such as Simple CPU communication or socket communication. More Details >>
- No:22294
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:00
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the connection configuration of FX5-CCL-MS
Connection is not allowed. For FX5-CCL-MS, only remote I/O stations, remote device stations andintelligent device stationscan be connected. More Details >>
- No:22316
- Release Date:2018/08/30 13:55
- Update:2023/07/03 17:19
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding communication supported by built-in RS-485 port
N:N Network, Parallel Link, MC protocol, Non-protocol communication, MELSOFT connection, MODBUS RTU, and Predefined protocol support are available. More Details >>
- No:22322
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:16
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the effect of battery voltage drop on logging function
Since the battery retains clock data even after power failure, the time of logging data may change. More Details >>
- No:39310
- Release Date:2023/01/12 16:53
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding number of input/output points when adding safety extension module
It will. It is treated the same as an intelligent module, so it occupies 8 I/O points. The safety input expansion module FX5-SF-8DI4 does not occupy the numb... More Details >>
- No:39314
- Release Date:2023/01/12 16:54
- Category: MELSEC iQ-F Series , CPU Module , Safety Control