FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series
FAQ
Keyword Search
FAQ within [ MELSEC iQ-F Series ]
-
Regarding the line tracing function
It is not supported. More Details >>
- No:39323
- Release Date:2023/02/14 09:01
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding input of Differential Driver Output Type
It does not. The built-in high-speed counter function of the FX5U/FX5UC CPU module does not support DC5V input. DC5V input can be achieved by adding BUS con... More Details >>
- No:39350
- Release Date:2023/01/12 17:09
- Update:2025/03/07 13:25
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding reading Sample Comments for Expansion Adapters
You cannot. The expansion adapters does not support reading sample comments. More Details >>
- No:39352
- Release Date:2023/02/15 10:16
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the parallel link function between CPU modules
Parallel linking between FX5 and FX3 CPU modules is not available. The N:N Network function supports communication between the FX5 CPU module and the FX3 CPU... More Details >>
- No:39364
- Release Date:2023/02/15 13:05
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding Email function Attachments
The file formats and file sizes that can be attached by the email function are as follows: ・Attachments: Up to one file ・File formats: Binary, ASCII, CSV... More Details >>
- No:40057
- Release Date:2023/08/25 10:21
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding automatic transfer of Data Logging Files
Data logging file transfer (FTP server auto transfer) is supported with the following firmware versions. ・FX5U/FX5UC CPU Module Ver. 1.300 or later ・FX5U... More Details >>
- No:44334
- Release Date:2024/03/20 13:30
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding Input Response Frequency Difference between FX5-2HC/ES and Conventional Model (FX3U-2HC)
The input response frequencies of the FX5-2HC/ES and FX3U-2HC differ as shown below. FX5-2HC/ES・・・2MHz FX3U-2HC・・・200kHz More Details >>
- No:44340
- Release Date:2024/03/20 13:31
- Category: MELSEC iQ-F Series , High-Speed Counter
-
Regarding FX5-ENET, FX5-ENET/IP IP addresses
You cannot configure two IP addresses. More Details >>
- No:44356
- Release Date:2024/03/27 15:56
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding checking latch settings
You can find it in the Advanced Settings section of GX Works3. Use the following procedure to display the Device (High Speed) settings. From the GX Wor... More Details >>
- No:44364
- Release Date:2024/03/27 16:05
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding compatible version of CANopen communication function for PDO communication
It is necessary to use the following CPU module, FX5-CCLGN-MS, GX Works3 versions. FX5-CCLGN-MS・・・1.020 or later FX5U/FX5UC CPU module ・・・1.260 or later ... More Details >>
- No:44473
- Release Date:2024/07/02 19:06
- Category: MELSEC iQ-F Series , Network/Communication