Regarding performing Data Logging with Special Relays
It's possible. Using special relays, it is possible to perform data logging from a program. For details, see the manual below. MELSEC iQ-F FX5 User's Manu... More Details >>
- No:39327
- Release Date:2023/02/14 09:05
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding Instruction processing time when the program capacity: 128 K steps are set
LD instruction: 0.35 μs, MOV instruction: 0.779 μs. For other instructions, see the manual below. MELSEC iQ-F FX5 Programming Manual (Instructions, Standa... More Details >>
- No:39362
- Release Date:2023/01/12 17:12
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding Device Memory Export/Import
Imports are not supported. Only exports are supported. More Details >>
- No:40027
- Release Date:2023/08/24 14:38
- Category: MELSEC iQ-F Series , Engineering Software
-
Regarding communication testing of Certificate Configuration Tool for FX5-ENET
The following are possible causes for communication not being established between the Certificate Configuration Tool for FX5-ENET and FX5-ENET. (1) Connecte... More Details >>
- No:40075
- Release Date:2023/08/25 09:06
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding cable diversion to FX5-2HC/ES
The cable cannot be used because the connector shape is different, so change the wiring. FX5-2HC/ES is a spring clamp terminal block, and FX3U-2HC is a MIL-... More Details >>
- No:44337
- Release Date:2024/03/20 13:26
- Category: MELSEC iQ-F Series , High-Speed Counter
-
Regarding TPDO and RPDO allocation
RWr is allocated to TPDO and RWw is allocated to RPDO. More Details >>
- No:44479
- Release Date:2024/07/02 19:06
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the Connected/Disconnected Module Detection button on FX5-CCLGN-MS
For the Connected/Disconnected Module Detection of FX5-CCLGN-MS, the network configuration of the subsequent stages can not be automatically detected unless ... More Details >>
- No:39274
- Release Date:2023/01/12 16:45
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the change of settings for reserved station (master station) of FX5-CCLGN-MS
FX5-CCLGN-MS allows the master station to change the reserved station setting with parameters, but the setting can not be changed by program. Note that link... More Details >>
- No:39275
- Release Date:2023/01/12 16:46
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the connection between FX5-CCLGN-MS and SLMP-compatible devices
The SLMP communication frames supported by the FX5-CCLGN-MS are 3E and 4E frames. When SLMP communication is performed from an SLMP-compatible device to the... More Details >>
- No:39280
- Release Date:2023/01/12 16:48
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the effect of battery voltage drop on logging function
Since the battery retains clock data even after power failure, the time of logging data may change. More Details >>
- No:39310
- Release Date:2023/01/12 16:53
- Category: MELSEC iQ-F Series , CPU Module