FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series
FAQ
Keyword Search
FAQ within [ MELSEC iQ-F Series ]
-
Regarding the maximum number of controllable axes of the bulit-in positioning function
Up to 4 axes can be controlled. Please use a transistor output type CPU module. (By adding a high speed pulse input/output module, maximum 12 axes (CPU bui... More Details >>
- No:22300
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:52
- Category: MELSEC iQ-F Series , CPU Module , Motion/Positioning
-
Regarding changing the current value of the high-speed counter.
To rewrite the current value, arbitrary values can be written using the DHCMOV instruction. (Example) Set the current value of the high-speed counter ch1 ... More Details >>
- No:22303
- Release Date:2018/08/30 13:55
- Update:2023/02/06 17:05
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding how to generate a false error
There is no function to generate a false error. For example, if operand (s2): divisor is set to "0" in the division command and the command is executed, err... More Details >>
- No:44610
- Release Date:2024/11/28 16:11
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the range of latch devices
The latch range can be set arbitrarily by the customer. The settings can be found in the memory/device settings of CPU parameters. To back up the link regist... More Details >>
- No:22297
- Release Date:2018/08/30 13:55
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding error 2440H on CPU module when using FX5-CCLGN-MS
When the power is turned on, the FX5-CCLGN-MS performs parameter check processing, and if an error occurs, the CPU module is also notified of the error. Ther... More Details >>
- No:39282
- Release Date:2023/01/12 16:49
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding clearing error with SM50
It is cleared by eliminating the cause of the error during detection and turning on SM50. For the error codes that can be cleared on the SM50, refer to the ... More Details >>
- No:39292
- Release Date:2023/02/13 15:37
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding CC-Link IE Field Network Basic Refresh Settings
You can't. Device allocation for refresh settings is sequential only. More Details >>
- No:39306
- Release Date:2023/02/13 16:41
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the COM terminal of the multiple input module
Yes, it's connected internally. More Details >>
- No:39318
- Release Date:2023/01/12 16:54
- Category: MELSEC iQ-F Series , Analog
-
Regarding program execution using SD Memory Cards
It's possible. Use the boot operation function of the SD memory card. *To use the boot operation function with the FX5S CPU module, you need to install an a... More Details >>
- No:39311
- Release Date:2023/02/14 08:54
- Category: MELSEC iQ-F Series , Option , CPU Module
-
Regarding the link refresh settings of FX5-CCL-MS
It is possible to use latch devices or I/O devices (X/Y) for link refresh devices. However, when using I/O devices (X/Y), use I/O numbers (such as X1000 ~/Y... More Details >>
- No:22308
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:37
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software , Network/Communication