FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series
FAQ
Keyword Search
FAQ within [ MELSEC iQ-F Series ]
-
Regarding the communication execution status output device for ADPRW instructions
It does not turn OFF automatically. Use the RST command in the program to turn it OFF. More Details >>
- No:39349
- Release Date:2023/02/15 10:07
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Yes, it is possible. Please consider functions such as Simple CPU communication or socket communication. More Details >>
- No:22294
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:00
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
CC-Link IE field When a network such as Network Basic is interrupted, the CPU module does not stop and continues to run. When the CC-Link IE Field Network i... More Details >>
- No:44611
- Release Date:2024/11/28 16:11
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the number of available channels of the built-in high speeed counters.
The high-speed counter supports 1-phase 1-input, 1-phase 2-input, 2-phase 2-input. The built-in counter in the CPU module can input up to 8ch. However,... More Details >>
- No:22310
- Release Date:2018/08/30 13:55
- Update:2023/02/13 11:42
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding the frequency of high-speed counters
The maximum frequency of the FX5U/FX5UC CPU module is 200kHz and the maximum frequency of the FX5S/FX5UJ CPU module is 100 kHz. More Details >>
- No:22312
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:18
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding the differences between Latches (1) and (2)
Whether the latch range is set by default is different. ・Latch (1) — Latch range is set by default. This can be changed at any time. ・Latch (2) — No latch ... More Details >>
- No:39351
- Release Date:2023/02/15 13:08
- Update:2024/08/19 09:54
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding setting the FX5 CPU Module that does not support the simple CPU communication function
When connecting 2 FX5 CPU Modules (firmware version 1.110 or later) that support the Simple CPU communication function and 2 FX5 CPU Modules (firmware vers... More Details >>
- No:44329
- Release Date:2024/03/20 13:35
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the built-in analog input/output function
FX5U CPU module has 2 built-in voltage input channels (DC0~10V) and 1 built-in voltage output channel (DC0~10V). If an external resister is connected, the m... More Details >>
- No:22313
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:47
- Category: MELSEC iQ-F Series , CPU Module , Analog
-
Regarding the type of battery which can be used with the CPU module.
FX3U-32BL can be used. The battery is not included with the CPU modu... More Details >>
- No:22285
- Release Date:2018/08/30 13:55
- Category: MELSEC iQ-F Series , Option , CPU Module
-
The FX3 intelligent function modules cannot be selected from the Element selection window because it does not correspond to the parameter setting of GX Works... More Details >>
- No:22304
- Release Date:2018/08/30 13:55
- Update:2024/08/19 09:50
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
221-230 of Total 266