Regarding scan time adjustment for replacing the FX3 Series
You can adjust by setting the constant scan in iQ-F series. Setting procedure: Navigation window > [Parameter] > [Module model name] > [CPU Paramet... More Details >>
- No:44866
- Release Date:2025/03/18 10:24
-
Regarding Recommended Substitute Models for FX3G-CNV-ADP
The FX5 CPU modules allows you to add an expansion adapter without using a connector conversion adapter. Therefore, there is no Recommended Substitute Models... More Details >>
- No:44875
- Release Date:2025/03/18 10:27
-
Regarding the built-in analog input/output function
FX5U CPU module has 2 built-in voltage input channels (DC0~10V) and 1 built-in voltage output channel (DC0~10V). If an external resister is connected, the m... More Details >>
- No:22313
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:47
-
Regarding Extended File Register (ER) file names
File names can not be changed. It is fixed to EXFILER.ERD. More Details >>
- No:39296
- Release Date:2023/02/13 16:39
-
Regarding the differences between Latches (1) and (2)
Whether the latch range is set by default is different. ・Latch (1) — Latch range is set by default. This can be changed at any time. ・Latch (2) — No latch ... More Details >>
- No:39351
- Release Date:2023/02/15 13:08
- Update:2024/08/19 09:54
-
It represents the number of characters that can be written. By changing "(32)," you can write up to 255 characters. More Details >>
- No:39353
- Release Date:2023/02/15 10:07
-
The following points are different for the iQ-F series. ・Error History If the FX5 CPU Module is turned off, the error history is cleared. ・Setting detail... More Details >>
- No:44335
- Release Date:2024/03/20 13:21
-
Regarding how to compare multiple word devices
It is possible to compare multiple word devices using the BKCMP_□ instruction. *where □ is the comparison symbol. Example:To compare 10 stores from D0 to D... More Details >>
- No:44616
- Release Date:2024/11/28 16:13
-
Regarding number of CC-Link IE field network Basic connections
When the FX5 CPU Module is used as the master station, the maximum number of devices connected to 1 network is 16. The following firmware versions are requi... More Details >>
- No:44652
- Release Date:2025/03/18 10:22
-
Regarding whether ladder monitoring is enabled by the Web server function
You cannot use the ladder monitor with the Web server function. With the Web server function, it is possible to monitor the device value, test the device (w... More Details >>
- No:44873
- Release Date:2025/03/18 10:23