- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > CPU Module
FAQ
Keyword Search
FAQ within [ CPU Module ]
-
Regarding write speed during RUN
CC-Link IE field Network Basic communication interval can be set with special relay and special register. During debugging, adjust the communication interv... More Details >>
- No:44342
- Release Date:2024/03/20 13:39
-
Regarding Data Collection for Device Comments
It is not possible to collect device comments. More Details >>
- No:40030
- Release Date:2023/08/24 14:40
-
Regarding the maximum number of connections for MODBUS communication
32 stations can be connected when RS-485 port is used and only 1 station can be connected when RS-232 port is used. More Details >>
- No:22324
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:49
-
Regarding restrictions on the external input/output forced ON/OFF function
The following restrictions apply to the external input/output forced ON/OFF function. ・Since RUN contact setting is RUN/STOP by external signal, forced ON/O... More Details >>
- No:44332
- Release Date:2024/03/20 12:58
-
Regarding instruction Compatibility Between FX5 CPU modules
The instructions on the FX5 CPU module are compatible. Module-only instructions can be used only for CPU modules that support intelligent function units. More Details >>
- No:40042
- Release Date:2023/08/24 15:46
-
Regarding expansion of communication ports
It is possible to use the MODBUS serial communication with multiple channels. However, only 1 channel can be set as the master. The MODBUS serial communica... More Details >>
- No:22323
- Release Date:2018/08/30 13:55
- Update:2023/06/26 09:04
-
Regarding how to compare multiple word devices
It is possible to compare multiple word devices using the BKCMP_□ instruction. *where □ is the comparison symbol. Example:To compare 10 stores from D0 to D... More Details >>
- No:44616
- Release Date:2024/11/28 16:13
-
Regarding Instruction processing time when the program capacity: 128 K steps are set
LD instruction: 0.35 μs, MOV instruction: 0.779 μs. For other instructions, see the manual below. MELSEC iQ-F FX5 Programming Manual (Instructions, Standa... More Details >>
- No:39362
- Release Date:2023/01/12 17:12
-
Regarding terminal block reuse
Terminal blocks can not be reused. Please rewire it. More Details >>
- No:39365
- Release Date:2023/02/15 13:06
-
Regarding the number of expansion adapters and expansion board connections for FX5S CPU module
Up to 6 devices can be connected. Extension adapters/boards (Max. 2 units) + analog extension adapters (Max. 4 units). *Using an SD memory card module ... More Details >>
- No:39336
- Release Date:2023/02/14 17:13