FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > CPU Module
FAQ
Keyword Search
FAQ within [ CPU Module ]
-
Regarding CC-Link IE field network support of FX5 CPU module built-in Ethernet
The built-in Ethernet on the FX5 CPU module does not support CC-Link IE field networks. If you use a CC-Link IE field network, add an FX5-CCLIEF. *The FX5-... More Details >>
- No:44877
- Release Date:2025/03/18 10:30
-
Regarding number of CC-Link IE field network Basic connections
When the FX5 CPU Module is used as the master station, the maximum number of devices connected to 1 network is 16. The following firmware versions are requi... More Details >>
- No:44652
- Release Date:2025/03/18 10:22
-
Regarding how to generate a false error
There is no function to generate a false error. For example, if operand (s2): divisor is set to "0" in the division command and the command is executed, err... More Details >>
- No:44610
- Release Date:2024/11/28 16:11
-
Regarding signs of VAL Instructions
The sign is required in the VAL instruction and cannot be ignored. More Details >>
- No:44609
- Release Date:2024/11/28 16:11
-
Regarding remote I/O expansion for FX5S CPU module
It is possible to connect to remote I/O with CC-Link IE Field Network Basic. Up to 16 remote stations can be connected. More Details >>
- No:40041
- Release Date:2023/08/24 15:45
- Update:2025/03/13 10:08
-
Regarding USB Cable Recommendations
A recommended USB cable is provided. ・MR-J3USBCBL3M(3 m) ・GT09-C30USB-5P(3 m) (manufactured by Mitsubishi Electric System Service Co., Ltd.) More Details >>
- No:40040
- Release Date:2023/08/24 15:45
-
Regarding Input Interrupt Delay
The following versions support the input interrupt delay function and can delay the start of execution. ・FX5U/FX5UC Ver. 1.290 or later ・FX5UJ Ver. 1.050 o... More Details >>
- No:40037
- Release Date:2023/08/24 15:43
-
Regarding Statement and Note Types
PLC :it is written to the CPU module and consumes the number of steps. ・Without character - 3 steps ・With character : 4 + (Number of characters + 2 + 14) /... More Details >>
- No:40023
- Release Date:2023/08/24 15:39
-
Regarding the number of FX5-4A-ADP connections
Up to 4 FX5-4A-ADPs can be connected to an FX5U/FX5UC/FX5S CPU module. To connect 3 or more FX5-4A-ADPs, the FX5-4A-ADP must have a serial number S/N: 224... More Details >>
- No:39348
- Release Date:2023/02/15 10:16
-
Regarding the effect of battery voltage drop on logging function
Since the battery retains clock data even after power failure, the time of logging data may change. More Details >>
- No:39310
- Release Date:2023/01/12 16:53
151-160 of Total 185