Regarding clearing the maximum and minimum scan times
It can be cleared with the scan time clear function. You can clear maximum and minimum scan time with GX Works3 Ver. 1.085 P or later or by special relays. More Details >>
- No:39342
- Release Date:2023/02/15 10:05
-
Regarding the number of available channels of the built-in high speeed counters.
The high-speed counter supports 1-phase 1-input, 1-phase 2-input, 2-phase 2-input. The built-in counter in the CPU module can input up to 8ch. However,... More Details >>
- No:22310
- Release Date:2018/08/30 13:55
- Update:2023/02/13 11:42
-
Regarding terminal block reuse
Terminal blocks can not be reused. Please rewire it. More Details >>
- No:39365
- Release Date:2023/02/15 13:06
-
It is used for switching between Sink/Source input. For sink input wiring, connect with "24V" terminal and short-circuit the "0V" and "input X***". For sou... More Details >>
- No:22286
- Release Date:2018/08/30 13:55
- Update:2022/12/22 09:39
-
Regarding how to Monitor Buffer Memory Values
You can monitor buffer memory values in the Ladder Editor by setting in GX Works3 >Tools >Options > Monitor > Common Item > Monitor Buffer Mem... More Details >>
- No:39324
- Release Date:2023/01/12 16:56
-
Regarding clearing error with SM50
It is cleared by eliminating the cause of the error during detection and turning on SM50. For the error codes that can be cleared on the SM50, refer to the ... More Details >>
- No:39292
- Release Date:2023/02/13 15:37
-
Regarding EtherCAT Communications
The FX5 CPU module does not support EtherCAT communication. There are no products in the FX series or iQ-F series that support EtherCAT communication. More Details >>
- No:39313
- Release Date:2023/02/14 08:54
-
Regarding the communication execution status output device for ADPRW instructions
It does not turn OFF automatically. Use the RST command in the program to turn it OFF. More Details >>
- No:39349
- Release Date:2023/02/15 10:07
-
Regarding Instruction description help in GX Works3
You can open the descriptions for each instruction by moving the cursor to the target instruction and pressing F1. You can also hover the cursor over it and ... More Details >>
- No:39366
- Release Date:2023/02/15 13:06
-
Regarding I/O assignment on the module configuration diagram of GX Works3
While the module configuration window is being displayed, the I/O assignment can be checked by selecting the following options from the menu bar: [Edit]→[X... More Details >>
- No:22307
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:25