FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > CPU Module
FAQ
Keyword Search
FAQ within [ CPU Module ]
-
Regarding the number of expansion adapters and expansion board connections for FX5S CPU module
Up to 6 devices can be connected. Extension adapters/boards (Max. 2 units) + analog extension adapters (Max. 4 units). *Using an SD memory card module ... More Details >>
- No:39336
- Release Date:2023/02/14 17:13
-
Regarding Statement and Note Types
PLC :it is written to the CPU module and consumes the number of steps. ・Without character - 3 steps ・With character : 4 + (Number of characters + 2 + 14) /... More Details >>
- No:40023
- Release Date:2023/08/24 15:39
-
EN (enable input) ・・・ This is the execution condition of the function. The function with EN is executed only if the execution condition of EN... More Details >>
- No:40024
- Release Date:2023/08/24 14:35
-
Regarding Display Module Support
In the iQ-F series, there is no lineup of display modules. Consider usingweb server function. More Details >>
- No:40045
- Release Date:2023/08/24 15:53
- Update:2023/08/24 15:56
-
Regarding using the connector of the CPU Module
The input/output cables used in the FX3GC and FX3UC basic units can be diverted to the FX5UC CPU Module (connector type). More Details >>
- No:44350
- Release Date:2024/03/27 15:44
-
Regarding the login screen for the Web Server Function
There is no setting or method to disable the login screen for the web server function. More Details >>
- No:44357
- Release Date:2024/03/27 15:52
-
Regarding the maximum number of channels of high-speed counters
The FX5 CPU module's built-in high-speed counter can control up to 8CH. Up to 16CH can be controlled by adding 4 modules of FX5-16ET/E□-H (high-speed pulse ... More Details >>
- No:22311
- Release Date:2018/08/30 13:55
- Update:2023/02/13 15:34
-
Regarding performing Data Logging with Special Relays
It's possible. Using special relays, it is possible to perform data logging from a program. For details, see the manual below. MELSEC iQ-F FX5 User's Manu... More Details >>
- No:39327
- Release Date:2023/02/14 09:05
-
Regarding the FX5S CPU Module Line-up
The line-up of input and output points of the FX5S CPU module is as follows. ・30 points (Input: 16 points, Output: 14 points) ・40 points (Input: 24 points,... More Details >>
- No:39340
- Release Date:2023/02/14 17:28
-
It cannot. Because there will be two CC-link IE field network Basic master stations in a network. More Details >>
- No:39346
- Release Date:2023/02/15 10:05
- Update:2024/04/25 10:10