Regarding comparison of Strings
Use the string comparison instructions LD$□, AND$□, OR$□. □contains =, <>, >, < =, <, > =. More Details >>
- No:39355
- Release Date:2023/02/15 13:03
-
Regarding the compatible programming tool
GX Developer/GX Works2 cannot be used. MELSEC iQ-F series only supports GX Works3. More Details >>
- No:22292
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:34
-
Regarding changing the current value of the high-speed counter.
To rewrite the current value, arbitrary values can be written using the DHCMOV instruction. (Example) Set the current value of the high-speed counter ch1 ... More Details >>
- No:22303
- Release Date:2018/08/30 13:55
- Update:2023/02/06 17:05
-
Regarding number of input/output points when adding safety extension module
It will. It is treated the same as an intelligent module, so it occupies 8 I/O points. The safety input expansion module FX5-SF-8DI4 does not occupy the numb... More Details >>
- No:39314
- Release Date:2023/01/12 16:54
-
Regarding the input circuit wiring of the FX5 CPU module
Yes. There is no problem using an external power supply for the input circuit of the FX5 CPU module. More Details >>
- No:39317
- Release Date:2023/02/14 08:56
-
Regarding the number of FX5-4A-ADP connections
Up to 4 FX5-4A-ADPs can be connected to an FX5U/FX5UC/FX5S CPU module. To connect 3 or more FX5-4A-ADPs, the FX5-4A-ADP must have a serial number S/N: 224... More Details >>
- No:39348
- Release Date:2023/02/15 10:16
-
Regarding changing the current address (user unit, pulse unit)
It can be changed. It is now possible to write to the address (user unit, pulse unit) by the DHCMOV command. However, writing is disabled during positioning... More Details >>
- No:39356
- Release Date:2023/02/15 13:03
-
Regarding using the 2nsec Clock Timer
The value of n can be set in SD414, and the range is from K1 to K32767. (Default value: K30) If n=K1, it is a 2-second clock timer with 1 second ON/1 second... More Details >>
- No:40019
- Release Date:2023/08/24 14:29
-
Regarding the type of battery which can be used with the CPU module.
FX3U-32BL can be used. The battery is not included with the CPU modu... More Details >>
- No:22285
- Release Date:2018/08/30 13:55
-
Regarding the specifications of the built-in Ethernet function of FX5 CPU module
The connection using the Ethernet port can establish a total of 8 connections which includes SLMP, MELSOFT connection, MODBUS/TCP, socket communication, and ... More Details >>
- No:22320
- Release Date:2018/08/30 13:55
- Update:2023/07/04 15:52