Regarding the compatible programming tool
GX Developer/GX Works2 cannot be used. MELSEC iQ-F series only supports GX Works3. More Details >>
- No:22292
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:34
-
Yes, it is possible. Please consider functions such as Simple CPU communication or socket communication. More Details >>
- No:22294
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:00
-
Regarding the necessity of using a battery
Device back up is available without using a battery. However, to back up link register (W) and file register (R) devices, a FX3U-32BL (battery) is required.... More Details >>
- No:22296
- Release Date:2018/08/30 13:55
- Update:2022/12/22 09:55
-
Regarding the maximum number of controllable axes of the bulit-in positioning function
Up to 4 axes can be controlled. Please use a transistor output type CPU module. (By adding a high speed pulse input/output module, maximum 12 axes (CPU bui... More Details >>
- No:22300
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:52
-
Regarding CW/CCW(Forward pulse/Reverse pulse) output of the built-in positioning function
FX5U/FX5UC/FX5S CPU modules are supported. Up to 2 axes are available in GX Works3 parameter settings. In addition, up to 8 axes can be added by adding a hi... More Details >>
- No:22306
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:48
-
Regarding the settings of built-in analog function of FX5U CPU module
The settings can be done using the parameter settings of GX Works3 or by settings the special relay/special registers. For further details please refer to M... More Details >>
- No:22314
- Release Date:2018/08/30 13:55
- Update:2023/06/26 09:20
-
Regarding the digital output of the built-in analog function
It is possible by setting the scaling function or shift function from the parameter settings. More Details >>
- No:22315
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:46
-
Regarding communication supported by built-in RS-485 port
N:N Network, Parallel Link, MC protocol, Non-protocol communication, MELSOFT connection, MODBUS RTU, and Predefined protocol support are available. More Details >>
- No:22322
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:16
-
Regarding expansion of communication ports
It is possible to use the MODBUS serial communication with multiple channels. However, only 1 channel can be set as the master. The MODBUS serial communica... More Details >>
- No:22323
- Release Date:2018/08/30 13:55
- Update:2023/06/26 09:04
-
Regarding the maximum number of connections for MODBUS communication
32 stations can be connected when RS-485 port is used and only 1 station can be connected when RS-232 port is used. More Details >>