- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > CPU Module
FAQ
Keyword Search
FAQ within [ CPU Module ]
-
Regarding dedicated instruction for JOG operation
There is no dedicated instruction to drive JOG. Use PLSV (variable speed operation) when operating JOG. More Details >>
- No:44355
- Release Date:2024/03/27 15:50
-
Regarding how to update the firmware of the FX5 CPU module
FX5U/FX5UC/FX5UJ CPU modules cannot perform firmware update using GX Works3. Use the SD memory card to update the firmware. However, the FX5S CPU module sup... More Details >>
- No:39325
- Release Date:2023/02/14 09:03
-
Regarding the driving contacts of high-speed counter instructions
The current value of the high-speed counter is retained and will not be cleared. More Details >>
- No:39304
- Release Date:2023/02/13 16:40
-
Regarding I/O assignment on the module configuration diagram of GX Works3
While the module configuration window is being displayed, the I/O assignment can be checked by selecting the following options from the menu bar: [Edit]→[X... More Details >>
- No:22307
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:25
-
Regarding reading Sample Comments for Expansion Adapters
You cannot. The expansion adapters does not support reading sample comments. More Details >>
- No:39352
- Release Date:2023/02/15 10:16
-
Regarding Control response parameter of built-in PID Control of CPU Module
The control response parameter can set the response to the target value (SV) of PID control as either "normal" or "fast". The difference is as follows. (1)W... More Details >>
- No:44653
- Release Date:2025/03/18 10:23
-
Regarding FX5 CPU Module clock settings
There are three types of configuration: GX Works3, special devices (SM/SD), and instructions. ・How to Configure in GX Works3 (1) In GX Works3, select On... More Details >>
- No:44365
- Release Date:2024/03/27 17:01
-
Regarding the type of Ethernet connection cable
Ethernet standard-compatible cable, category 5 or higher (STP cable) can be used. *Straight cable can be used. When connecting directly to the computer, cr... More Details >>
- No:22295
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:23
-
CC-Link IE field When a network such as Network Basic is interrupted, the CPU module does not stop and continues to run. When the CC-Link IE Field Network i... More Details >>
- No:44611
- Release Date:2024/11/28 16:11
-
Regarding how to clear simple CPU communication function errors
After removing the error factor, you can clear it by executing "Clear latest error code" from "Diagnostic" - "Simple CPU Communication Diagnostic" in GX Work... More Details >>
- No:40049
- Release Date:2023/08/25 09:06