- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > CPU Module
FAQ
Keyword Search
FAQ within [ CPU Module ]
-
Regarding number of CC-Link IE field network Basic connections
When the FX5 CPU Module is used as the master station, the maximum number of devices connected to 1 network is 16. The following firmware versions are requi... More Details >>
- No:44652
- Release Date:2025/03/18 10:22
-
Regarding bit specification index modification for word devices
Index modification cannot be done for bit specifications for Word device. More Details >>
- No:39299
- Release Date:2023/02/13 16:39
-
Regarding Data Register Byte Splitting
Use the WTOB instruction. More Details >>
- No:40022
- Release Date:2023/08/24 14:32
-
Regarding SFC Language Support
The FX5 CPU module supports SFC language with the following firmware versions. ・FX5U/FX5UC Ver. 1.220 or later ・FX5UJ Ver. 1.050 or later ・FX5S Ver. 1.010... More Details >>
- No:40043
- Release Date:2023/08/24 15:47
-
Regarding dedicated instruction for JOG operation
There is no dedicated instruction to drive JOG. Use PLSV (variable speed operation) when operating JOG. More Details >>
- No:44355
- Release Date:2024/03/27 15:50
-
Regarding Control response parameter of built-in PID Control of CPU Module
The control response parameter can set the response to the target value (SV) of PID control as either "normal" or "fast". The difference is as follows. (1)W... More Details >>
- No:44653
- Release Date:2025/03/18 10:23
-
Regarding the system configuration of FX5-CCL-MS with FX5 CPU module
A total of two FX5-CCL-MS (CC-Link system master/intelligent device) can be connected: one as a master station and one as an intelligent device station. More Details >>
- No:22318
- Release Date:2018/08/30 13:55
- Update:2023/07/03 11:50
-
Regarding the specifications of the built-in Ethernet function of FX5 CPU module
The connection using the Ethernet port can establish a total of 8 connections which includes SLMP, MELSOFT connection, MODBUS/TCP, socket communication, and ... More Details >>
- No:22320
- Release Date:2018/08/30 13:55
- Update:2023/07/04 15:52
-
Regarding clearing the maximum and minimum scan times
It can be cleared with the scan time clear function. You can clear maximum and minimum scan time with GX Works3 Ver. 1.085 P or later or by special relays. More Details >>
- No:39342
- Release Date:2023/02/15 10:05
-
Regarding instructions for converting 16 bit data to single-precision real numbers
There is. Please use the INT2FLT instruction. More Details >>
- No:39309
- Release Date:2023/02/13 18:22
71-80 of Total 185