Regarding the effect of battery voltage drop on logging function
Since the battery retains clock data even after power failure, the time of logging data may change. More Details >>
- No:39310
- Release Date:2023/01/12 16:53
-
Regarding number of input/output points when adding safety extension module
It will. It is treated the same as an intelligent module, so it occupies 8 I/O points. The safety input expansion module FX5-SF-8DI4 does not occupy the numb... More Details >>
- No:39314
- Release Date:2023/01/12 16:54
-
Regarding GX Works3 Module configuration diagram
It can't be configured. In the module configuration diagram of GX Works3, the configurations that can be created are those excluding FX5-CNV-IFC and FX3 Int... More Details >>
- No:39331
- Release Date:2023/02/14 09:08
-
It represents the number of characters that can be written. By changing "(32)," you can write up to 255 characters. More Details >>
- No:39353
- Release Date:2023/02/15 10:07
-
Regarding Instruction description help in GX Works3
You can open the descriptions for each instruction by moving the cursor to the target instruction and pressing F1. You can also hover the cursor over it and ... More Details >>
- No:39366
- Release Date:2023/02/15 13:06
-
Regarding using the 2nsec Clock Timer
The value of n can be set in SD414, and the range is from K1 to K32767. (Default value: K30) If n=K1, it is a 2-second clock timer with 1 second ON/1 second... More Details >>
- No:40019
- Release Date:2023/08/24 14:29
-
Regarding number of CC-Link IE field network Basic connections
When the FX5 CPU Module is used as the master station, the maximum number of devices connected to 1 network is 16. The following firmware versions are requi... More Details >>
- No:44652
- Release Date:2025/03/18 10:22
-
Regarding Control response parameter of built-in PID Control of CPU Module
The control response parameter can set the response to the target value (SV) of PID control as either "normal" or "fast". The difference is as follows. (1)W... More Details >>
- No:44653
- Release Date:2025/03/18 10:23
-
Regarding I/O assignment on the module configuration diagram of GX Works3
While the module configuration window is being displayed, the I/O assignment can be checked by selecting the following options from the menu bar: [Edit]→[X... More Details >>
- No:22307
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:25
-
Regarding the digital output of the built-in analog function
It is possible by setting the scaling function or shift function from the parameter settings. More Details >>
- No:22315
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:46