FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC iQ-F Series > Network/Communication
FAQ
Keyword Search
FAQ within [ Network/Communication ]
-
Regarding the login screen for the Web Server Function
There is no setting or method to disable the login screen for the web server function. More Details >>
- No:44357
- Release Date:2024/03/27 15:52
-
Reagrding specifying an FTP client domain
The iQ-F series does not support domain specification, so specify the IP address. More Details >>
- No:44359
- Release Date:2024/03/27 15:58
-
Regarding number of CC-Link IE field network Basic connections
When the FX5 CPU Module is used as the master station, the maximum number of devices connected to 1 network is 16. The following firmware versions are requi... More Details >>
- No:44652
- Release Date:2025/03/18 10:22
-
Regarding CC-Link IE field network support of FX5 CPU module built-in Ethernet
The built-in Ethernet on the FX5 CPU module does not support CC-Link IE field networks. If you use a CC-Link IE field network, add an FX5-CCLIEF. *The FX5-... More Details >>
- No:44877
- Release Date:2025/03/18 10:30
-
Regarding CC-Link IE Field Network Basic Refresh Settings
You can't. Device allocation for refresh settings is sequential only. More Details >>
- No:39306
- Release Date:2023/02/13 16:41
-
Regarding the system configuration of FX5-CCL-MS with FX5 CPU module
A total of two FX5-CCL-MS (CC-Link system master/intelligent device) can be connected: one as a master station and one as an intelligent device station. More Details >>
- No:22318
- Release Date:2018/08/30 13:55
- Update:2023/07/03 11:50
-
Regarding the differences between CC-Link IE TSN and CC-Link IE Field Networks
(1)Whether or not networks can be mixed on the same trunk line is different. CC-Link IE TSN allows network mixing on the same trunk line. When using a CC-Li... More Details >>
- No:39359
- Release Date:2023/01/12 17:10
-
Regarding setting the FX5 CPU Module that does not support the simple CPU communication function
When connecting 2 FX5 CPU Modules (firmware version 1.110 or later) that support the Simple CPU communication function and 2 FX5 CPU Modules (firmware vers... More Details >>
- No:44329
- Release Date:2024/03/20 13:35
-
Regarding the maximum number of connections for MODBUS communication
32 stations can be connected when RS-485 port is used and only 1 station can be connected when RS-232 port is used. More Details >>
- No:22324
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:49
-
Regarding communication supported by built-in RS-485 port
N:N Network, Parallel Link, MC protocol, Non-protocol communication, MELSOFT connection, MODBUS RTU, and Predefined protocol support are available. More Details >>
- No:22322
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:16
71-80 of Total 97