  • Inching operation

    Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>

    • No:23590
    • Release Date:2018/09/14 15:09
  • Degree axis

    Yes. (1) Absolute system (a) When the software stroke limit is invalid Positioning is carried out in a designated direction by "[Cd.40] ABS direction in deg... More Details >>

    • No:23601
    • Release Date:2018/09/14 15:09
  • Restart

    Set "[Cd.6] Restart command" to "1". More Details >>

    • No:23619
    • Release Date:2018/09/14 15:09
  • Torque limit

    Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>

    • No:23591
    • Release Date:2018/09/14 15:09
  • Electronic gear

    Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>

    • No:23586
    • Release Date:2018/09/14 15:09
  • Motor rotation direction

    Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>

    • No:23587
    • Release Date:2018/09/14 15:09
  • Servo amplifier forced stop

    Set "[PA04] Function selection A-1" to "_1_ _h: Invalid". More Details >>

    • No:23610
    • Release Date:2018/09/14 15:09
  • Current value change

    The following shows the procedure for changing the current value to a new value.(1) Write the new current value to "[Cd. 9] New current value".(2) Write "900... More Details >>

    • No:23585
    • Release Date:2018/09/14 15:09
  • Speed limit value

    No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>

    • No:23595
    • Release Date:2018/09/14 15:09
  • Servo status

    Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>

    • No:23588
    • Release Date:2018/09/14 15:09
    • Update:2023/03/09 10:02