  • Servo status

    Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>

    • No:23588
    • Release Date:2018/09/14 15:09
    • Update:2023/03/09 10:02
  • BUSY signal

    The BUSY signal turns ON even when position control of movement amount "0" is executed.However, since the ON time is short, the ON status may not be detected... More Details >>

    • No:23612
    • Release Date:2018/09/14 15:09
  • Home position address

    Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>

    • No:23599
    • Release Date:2018/09/14 15:09
  • Servo amplifier forced stop

    Set "[PA04] Function selection A-1" to "_1_ _h: Invalid". More Details >>

    • No:23610
    • Release Date:2018/09/14 15:09
  • Error 2035

    Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>

    • No:23616
    • Release Date:2018/09/14 15:09
  • Parameter initialization

    The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>

    • No:23602
    • Release Date:2018/09/14 15:09
  • Input/output signal

    Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>

    • No:23594
    • Release Date:2018/09/14 15:09
  • Torque limit

    Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>

    • No:23591
    • Release Date:2018/09/14 15:09
  • Restart

    Set "[Cd.6] Restart command" to "1". More Details >>

    • No:23619
    • Release Date:2018/09/14 15:09
  • Speed limit value

    No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>

    • No:23595
    • Release Date:2018/09/14 15:09