Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>
- No:23590
- Release Date:2018/09/14 15:09
-
Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>
- No:23616
- Release Date:2018/09/14 15:09
-
Set "[PA04] Function selection A-1" to "_1_ _h: Invalid". More Details >>
- No:23610
- Release Date:2018/09/14 15:09
-
The following shows the setting value details.• 1 to 600: Positioning data No.• 7000 to 7004: Block start designation• 9001: Machine home position return• 90... More Details >>
- No:23597
- Release Date:2018/09/14 15:09
-
Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>
- No:23599
- Release Date:2018/09/14 15:09
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>
- No:23588
- Release Date:2018/09/14 15:09
- Update:2023/03/09 10:02
-
Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>
- No:23587
- Release Date:2018/09/14 15:09
-
Set "[Cd.6] Restart command" to "1". More Details >>
- No:23619
- Release Date:2018/09/14 15:09
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>
- No:23602
- Release Date:2018/09/14 15:09
-
No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>
- No:23595
- Release Date:2018/09/14 15:09