FAQ within [ QD75MH ]

1-10 of Total 33

prev 1 / 4page next
  • Input/output signal

    Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>

    • No:23594
    • Release Date:2018/09/14 15:09
  • Parameter initialization

    The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>

    • No:23602
    • Release Date:2018/09/14 15:09
  • HPR request flag

    It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>

    • No:23617
    • Release Date:2018/09/14 15:09
  • Positioning start

    There are two ways to start a positioning operation: (1) Set the "[Cd.3] Positioning start No.", and turn ON the positioning start signal. (2) Use the dedica... More Details >>

    • No:23593
    • Release Date:2018/09/14 15:09
  • Speed change during JOG operation

    Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>

    • No:23606
    • Release Date:2018/09/14 15:09
  • Torque limit

    Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>

    • No:23591
    • Release Date:2018/09/14 15:09
  • Error 2035

    Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>

    • No:23616
    • Release Date:2018/09/14 15:09
  • Torque limit

    Set the torque limit value in "[Cd.101] Torque output setting value" before the positioning start.The values of "[Pr.17] Torque limit setting value" and "[Cd... More Details >>

    • No:23583
    • Release Date:2018/09/14 15:09
  • Servo status

    Yes. You can check the servo status through the following monitor data.• "[Md.108] Servo status"• "[Md.125] Servo status 3"• "[Md.500] Servo status 7" More Details >>

    • No:23588
    • Release Date:2018/09/14 15:09
  • Positioning start No.

    The following shows the setting value details.• 1 to 600: Positioning data No.• 7000 to 7004: Block start designation• 9001: Machine home position return• 90... More Details >>

    • No:23597
    • Release Date:2018/09/14 15:09