FAQ


FAQAbout Products
- FAQ > Controllers > Motion Controllers > MELSEC-Q Series > Positioning Modules > QD75MH
FAQ
Keyword Search
FAQ within [ QD75MH ]
-
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
- No:23594
- Release Date:2018/09/14 15:09
-
Refer to "b2: Command in-position flag" of "[Md.31] Status". More Details >>
- No:23598
- Release Date:2018/09/14 15:09
-
No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>
- No:23595
- Release Date:2018/09/14 15:09
-
Speed change during JOG operation
Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>
- No:23606
- Release Date:2018/09/14 15:09
-
Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>
- No:23591
- Release Date:2018/09/14 15:09
-
Error 1205 (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction se... More Details >>
- No:23614
- Release Date:2018/09/14 15:09
-
Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>
- No:23587
- Release Date:2018/09/14 15:09
-
Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>
- No:23616
- Release Date:2018/09/14 15:09
-
Set "[Cd.6] Restart command" to "1". More Details >>
- No:23619
- Release Date:2018/09/14 15:09
-
No. The motors' operation is not completely linked to ON/OFF timing of the BUSY signals.BUSY signal is turned ON when the controller starts sending commands ... More Details >>
- No:23611
- Release Date:2018/09/14 15:09
1-10 of Total 33