The torque limit value can be changed regardless of JOG operation status.Set the new torque limit value with "[Cd.22] New torque value". More Details >>
- No:23608
- Release Date:2018/09/14 15:09
-
There are two ways to start a positioning operation: (1) Set the "[Cd.3] Positioning start No.", and turn ON the positioning start signal. (2) Use the dedica... More Details >>
- No:23593
- Release Date:2018/09/14 15:09
-
Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value".When the current torque reaches the limit, "b... More Details >>
- No:23592
- Release Date:2018/09/14 15:09
-
Error1201 (HPR data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position return after checking ... More Details >>
- No:23604
- Release Date:2018/09/14 15:09
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>
- No:23588
- Release Date:2018/09/14 15:09
- Update:2023/03/09 10:02
-
Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>
- No:23599
- Release Date:2018/09/14 15:09
-
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
- No:23594
- Release Date:2018/09/14 15:09
-
Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>
- No:23590
- Release Date:2018/09/14 15:09
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>
- No:23602
- Release Date:2018/09/14 15:09
-
It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>
- No:23617
- Release Date:2018/09/14 15:09