FAQ within [ MELSEC-Q Series ]
-
Specifying steps in printing data displayed in the window in GX Works2
GX Works2 Version 1.45X or later supports a print range specifying capability.Set "Start Step" and "End Step" for "Specified Print Range" in the Print window. More Details >>
- No:22695
- Release Date:2018/09/03 17:29
-
Whether or not device indirect specifications in structured ladder programs are allowed
Indirect specifications with "@" cannot be used in structured ladder programs and the Structured Text. Use indirect specifications in a ladder language program. More Details >>
- No:22697
- Release Date:2018/09/03 17:29
-
Reading file registers in the standard RAM
Set Target Memory to "Standard RAM" in the Read from PLC window to select a file register file. More Details >>
- No:22552
- Release Date:2018/09/03 17:28
-
The corresponding operation depends on the counter type selected. (1) If "Linear Counter" is selected If the present counter value exceeds the upper limi... More Details >>
- No:22624
- Release Date:2018/09/03 17:29
- Update:2018/09/21 10:32
-
Operation error at the execution of a BIN instruction
Keep SM722 ON or correct the program so that any one of the ten numbers 0 to 9 is stored in each digit of the source data.An operation error occurs when data... More Details >>
- No:22635
- Release Date:2018/09/03 17:29
-
Open setting of the built-in Ethernet port QCPU
No.It is necessary to configure one port to use the MELSOFT connection. More Details >>
- No:22648
- Release Date:2018/09/03 17:29
-
Boot operation from the standard ROM in the universal model QCPU
The universal model QCPU modules have their standard ROM but boot operation from the standard ROM is impossible. Boot the module from a memory card. More Details >>
- No:22602
- Release Date:2018/09/03 17:29
- Update:2018/09/20 18:01
-
Ethernet communication after the replacement of an external device
Personal computers have different MAC addresses and an Ethernet module hold a MAC address. Hence the MAC address that the Ethernet module currently holds is ... More Details >>
- No:22665
- Release Date:2018/09/03 17:29
-
Detecting the connection between a built-in Ethernet port QCPU and hub
You can check the connection to the hub with bit 10 of the special register SD1288. When bit 10 of the SD1288 is on, the QCPU is in connection with the hub. More Details >>
- No:22712
- Release Date:2018/09/03 17:29
-
Boot operation from the standard ROM
The boot operation from the standard ROM is not possible.The program memory of universal model QCPU is a flash ROM.Thus, writing in the program memory achiev... More Details >>
- No:22553