FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
Support for Q series RS-232 cable
Yes. More Details >>
- No:22803
- Release Date:2018/09/03 17:30
-
Built-in positioning function of LCPU
The positioning operation starts just in 30 microseconds, with a maximum high speed output of 200k pulses per second. S-curve acceleration/deceleration is al... More Details >>
- No:22790
- Release Date:2018/09/03 17:30
-
Simultaneous broadcast transmission setting for built-in Ethernet port LCPU
To send simultaneous broadcast using UDP, set the parameters as follows.- Destination IP Address: FF.FF.FF.FFh - Destination Port Number: Other than FFFFh (S... More Details >>
- No:22785
- Release Date:2018/09/03 17:30
-
FNC connector pin layout in L series I/O module and Q series I/O module
Yes. They have the same pin layout. More Details >>
- No:22774
- Release Date:2018/09/03 17:30
-
The heater disconnection detection function monitors the heater current on the transistor output. If no current flows when the transistor is ON, it is consi... More Details >>
- No:22773
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:58
-
Availability of step ladders for FX in L series
Step ladders are not available in LCPU. There is no alternative function. More Details >>
- No:22752
- Release Date:2018/09/03 17:29
-
TCP retransmission timer setting for built-in Ethernet port LCPU
For the built-in Ethernet port in the L series CPU, the TCP retransmission timer setting is fixed and unchangeable. The retransmission occurs six times. The... More Details >>
- No:22745
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:52
-
The data logging file transfer function allows for transfer of the logging data to an upper server regularly. It is transferred when data logging is switched... More Details >>
- No:22741
- Release Date:2018/09/03 17:29
-
Communication data code of the MC protocol for the built-in Ethernet port in LCPU
The communication data code is selectable by the communication data code setting in [Parameter] -> [PLC Parameter] -> [Built-in Ethernet Port Setting]. More Details >>
- No:22735
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:22
-
Turning OFF the power with the battery error occurring
The error history will be deleted. More Details >>
- No:22734
- Release Date:2018/09/03 17:29
51-60 of Total 105