No. It is necessary to configure one port to use the MELSOFT connection. More Details >>
Use of 4E frame for built-in Ethernet...
The built-in Ethernet port in the L series is compatible only with the QnA-compatible 3E frame. The 4E frame is not supported. More Details >>
Connection status detection between a...
The bit 10 of the special register SD1288 provides the connection status to a hub. When the bit 10 of SD1288 is ON, a hub is connected. More Details >>
Availability of step ladders for FX i...
Step ladders are not available in LCPU. There is no alternative function. More Details >>
Use of an A-compatible 1E frame for t...
The built-in Ethernet port in the L series is compatible only with a QnA-compatible 3E frame of the MC protocol. An A-compatible 1E frame is not supported. More Details >>
Index modification when using extende...
It is not possible to specify index modification to cross over the boundary between the internal user device (D) and the extended data register (D). Change t... More Details >>
Retention of auto tuning setting valu...
Use the automatic backup setting. While "1: enabled" is set in the CH[] automatic backup setting after auto tuning of PID constants in the buffer memory (Un\... More Details >>
SD1284 of LCPU with built-in Ethernet...
The bits 0 to F of the special register SD1284 (Open request signal) correspond to the connection numbers 1 to 16. When the open request is sent, the corresp... More Details >>
Simultaneous broadcast reception sett...
To receive simultaneous broadcast using UDP, set the parameters as follows. - Destination IP Address: FF.FF.FF.FFh - Destination Port No.: Other than FFFFh (... More Details >>
Compliance with SEMI-F47 for L series...
Use the following power supply module with an input power of 200 VAC for compliance with SEMI-F47. - Power supply module: L61PWith an input power of 100 VAC,... More Details >>
71-80 of Total 105