CC-Link master modules' start I/O No. and refresh devices RX/RY
The I/O numbers used for I/O modules and intelligent function modules cannot be used as refresh targets for RX/RY. Use the I/O numbers greater than those use... More Details >>
- No:22997
- Release Date:2018/09/03 17:31
-
Settings required for transient transmission
The routing parameter settings are required for transient transmission to the CPU module with another network No. The request source station, relay station,... More Details >>
- No:22995
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:40
-
The number of CC-Link modules mountable with a universal model QCPU module
If the parameter is set, the following number of modules can be mounted at maximum. - Q00UJ/Q00U/Q01UCPU: Up to 2 modules - Q02UCPU: Up to 4 modules - Uni... More Details >>
- No:22981
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:20
-
QJ71E71-100's compatibility with the automatic cable type (straight or cross) recognizing function
QJ71E71-100 does not support the AutoMDI/MDI-X function (automatic cable type (straight or cross) recognizing feature). More Details >>
- No:22976
- Release Date:2018/09/03 17:31
-
Extending the station-to-station distance with a CC-Link IE controller
Use the optical media converter DMS-1000SL(-DC) (manufactured by Mitsubishi Electric System & Service Co., Ltd.). You can extend the station-to-station dista... More Details >>
- No:23067
- Release Date:2018/09/03 17:31
-
Data length for fixed buffer data communications by QJ71E71
The units of send data and receive data are shown below. - Fixed buffer data communications with the "Procedure Exist" control method: Words - Fixed buff... More Details >>
- No:23061
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:17
-
Unit of receive data used by the QJ71C24N series pre-defined protocol support function
The fixed data is used for specific codes and character strings such as a command. Setting a device is not required. More Details >>
- No:23049
- Release Date:2018/09/03 17:31
-
Whether or not multiple QJ72LP25-25 modules can be mounted
No, only a single QJ72LP25-25 can be mounted (and is to be mounted on the CPU slot on a main base unit). More Details >>
- No:23042
- Release Date:2018/09/03 17:31
-
Connecting QJ71C24N to an external device that has no DTR signal
Carry out DTR and DSR wiring that returns signals on QJ71C24N(-R2). More Details >>
- No:23039
- Release Date:2018/09/03 17:31
-
How to set CC-Link reserved stations
- If the Network Parameter is used Make "Station Information Setting". - If the parameter is set using a dedicated instruction Set the control data of... More Details >>
- No:22996
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:41