Parameter settings for a CC-Link master station and local stations
Local stations also need parameter settings. More Details >>
- No:22991
- Release Date:2018/09/03 17:31
-
Data length for fixed buffer data communications by QJ71E71
The units of send data and receive data are shown below. - Fixed buffer data communications with the "Procedure Exist" control method: Words - Fixed buff... More Details >>
- No:23061
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:17
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
-
Relation between CC-Link terminals and signal lines
The following shows the relations between CC-Link terminals and signal lines. - DA : Blue -DB: White -DG: Yellow More Details >>
- No:23077
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:11
-
How to make the expanded cyclic setting for CC-Link local stations
Make the expanded cyclic setting for a CC-Link local station using the programming tool, GX Developer or GX Works2. Follow the procedure below. (1) Set th... More Details >>
- No:23030
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:17
-
Difference in specifications between CC-Link versions
Ver.1.10 is a standard where CC-Link station-to-station cable length restriction in Ver. 1.00 has been removed, and the length of all station-to-station cabl... More Details >>
- No:22975
- Release Date:2018/09/03 17:31
-
Necessity of terminating resistors in CC-Link communication
No, it is unnecessary. Terminating resistors are only required at both ends of the network. More Details >>
- No:22966
- Release Date:2018/09/03 17:31
-
Mixing line topologies with star topologies in the CC-Link IE Field Network
Line topologies and star topologies can be mixed. More Details >>
- No:23059
- Release Date:2018/09/03 17:31
-
Buffer memory addresses of CC-Link modules
If the remote net Ver.1 mode is used, each station number is given fixed buffer memory addresses.If the remote net Ver.2 mode is used, different buffer memor... More Details >>
- No:22992
- Release Date:2018/09/03 17:31
-
Difference between QJ61BT11 and QJ61BT11N
QJ61BT11N supports Version 2 (expanded cyclic setting), the setting for refreshing/forced clearing a slave station data when the switch on a programmable con... More Details >>
- No:22964
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:16