SB/SW refresh device setting with CC-Link
There are no problems even though the SB/SW refresh device has not been set. More Details >>
- No:23080
- Release Date:2018/09/03 17:31
-
Terminating resistors for RS-422 communication of QJ71C24N
The resistance value is 330 ohm, 1/4 W. More Details >>
- No:22965
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:33
-
Mixing the CC-Link IE Field Network with general LAN communication
Mixed communication with the same hub cannot be established. Establish the CC-Link IE Field Network and general LAN communication separately. More Details >>
- No:22988
- Release Date:2018/09/03 17:31
- Update:2019/06/27 15:48
-
Terminating resistors for RS-485 communication of LJ71C24
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22999
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:25
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
-
Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>
- No:23009
- Release Date:2018/09/03 17:31
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
-
CC-Link signals checked when an error occurs
Check the following signals.- Module error signal : X0- Host data link status signal: X1- Other station data link status signal: X3 More Details >>
- No:23021
- Release Date:2018/09/03 17:31
-
MODE switch setting for QJ61BT11N
The MODE switch can set the following modes.- 0 to 4: Online mode- 5 to 9: Line test mode- A to E: Hardware test modeEach mode in ascending order of set valu... More Details >>
- No:23025
- Release Date:2018/09/03 17:31
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31